Micanan PRO-GH Manuel d'instructions Page 15

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 45
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 14
15
SECTION C: PRO-GH(E), PRO-GHC(E)Full feature logic board Smart 10.0
(UL325 2010 compliant)
Note: The operator is shipped from the factory in the D1 mode setting (constant pressure open and close). The operator
should remain in this mode until all connections and limit switch adjustments are completed.
POWER WIRING INSTRUCTIONS:
Connect primary power supply directly to the separate power terminal strip supplied using any of the 1-1/8” (2.85 cm)
diameter holes provided on control box. Do not connect power supply directly to the circuit board.
1. Single phase: Connect single-phase power supply to terminals L/L1 and N/L2 on three-pole power terminal strip
(110V or 220V 1-phase).
2. Three-phase: Connect three-phase power supply to terminals L1, L2 and L3 on three-pole power terminal strip
(208V, 230V, 380V, 460V or 575V).
ON BOARD O/C/S PBS INSTRUCTIONS:
On-board Open, Close and Stop buttons are provided directly on the board for installation and troubleshooting purposes. In
order to operate unit by on-board Open, Close, Stop buttons, the factory installed jumper (#1) between the COM and STOP
terminals on the terminal strip must remain connected.
MOTOR DIRECTION VERIFICATION:
Make sure the mode of operation is selected to D1.
After electrical power connections are made, manually move door to mid-position. Using the on-board buttons press the
“Open” button for several seconds and then press the “Stop” button. If door did not move in correct direction (or if limit
cams not moving in correct direction towards the open limit switch) see below:
For single-phase operators: The operators leave the factory with correct motor and limit shaft direction according to
standard door installations. However, for special fire door, through wall mounting or other special door applications, the
motor direction and limit switch direction may need to be reversed. A dipswitch (Dip #1) is provided to reverse direction of
motor and limit switch direction. If motor direction is reversed, the open and close limit switches are automatically reversed.
However, the advanced close limit switch needs to be manually changed. Disconnect the 2 wires from the advanced closed
limit switch and re-connect to the auxiliary limit switch provided.
Note: Ensure that when the on-board open button is depressed and the door moves in the correct open direction that
activation of the open limit switch illuminates the ‘’OPEN LIMIT” L.E.D and stops the door.
Vue de la page 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 44 45

Commentaires sur ces manuels

Pas de commentaire